Discussion in 'The Big Chill' started by 2ndgsx, Jul 7, 2011.

  1. 2ndgsx

    2ndgsx Member

    I have installed the ac system back on my 1971 gs and am having a problem with cooling. I insalled a new compressor,dryer,and expansion valve and 134a. I am not getting any cooling in the evaporator but the suction line is frosting up where the small line from the evaporator (oil bleed port) enters the poa valve to the compressor. I have 80 lbs pressure at valve port on poa valve. Is this a poa valve problem or restriction some where else?

    Mike
     
  2. SteeveeDee

    SteeveeDee Orange Acres

    What is your high side pressure?
     
  3. 2ndgsx

    2ndgsx Member

    100 lb on high side with compressor running, but I could only get 1 lb of freon in system. I charged system on low side at poa valve port compressor running (gas not liquid). It seems that all I can get in system is from charging port back into evaporator. Evaporator seems to be open when I blew compressed air in it.
     
  4. lsrx101

    lsrx101 Well-Known Member

  5. ceas350

    ceas350 "THE BURNER"

    Did you use a vacuum pump to remove air/ noncondensibles from the system?
     
  6. 2ndgsx

    2ndgsx Member

    Yes, 1hr and 30 mins vacuum.
     
  7. GStage1

    GStage1 Always looking for parts!

    Your POA valve must be recalibrated/flow tested for R134....will not work if you just changed over and did not reset the valve....will never blow cold at low rpm.
     